Классификация |
Protect C.1000R (S) |
Protect C.2000R (S) |
Protect C.3000R (S) |
Protect C.6000R |
Типовая мощность (Type power) |
1000 VA (cos φ = 0.7 lag) 700 В |
2000 VA (cos φ = 0.7 lag) 1400 В |
3000 VA (cos φ = 0.7 lag) 2100 В |
6000 VA (cos φ = 0.7 lag) 4200 В |
Вход |
Входное напряжение (Rated input voltage) |
220 / 230 /240 Vac |
Диап. входных напряжений в реж. без акк. бат. (Voltage tolerance range) |
160 Vac - 300 Vac ± 5 Vac Bypass 80 Vac - 264 Vac |
176 Vac - 276 Vac ± 3% Bypass 176 Vac - 261% |
Частота (Nominal frequency, Frequency tolerance range) |
50 Hz / 60 Hz (automatic detection) ± 4 Hz |
Ток потребления (макс.) (Curr. consumption (full load)) |
7 A |
10 A (12 A) |
16 A |
31 A |
Коэффициент мощности (Input power factor) |
λ ≥ 0.96 |
λ ≥ 0.98 |
Connection |
non-heating appliance connector |
Terminal block |
Overvoltage dataline protection |
RJ11 (phone, fax, modem) RJ45 (Ethernet 10/100 MBit/s) |
Выход |
Номинальное выходное напряжение (Rated output voltage) |
220 / 230 / 240 Vac ± 2% |
220 / 230 / 240 Vac ± 1% (configuration via software "CompuWatch") |
Частота (Nominal frequency) |
50 Hz / 60 Hz ± 0.2% |
50 Hz / 60 Hz ± 0.1% (depending on mains) |
Форма кривой напряжения (Voltage waveform) |
Pure sine wave Harmonic distortion: ≤ 4% THD (linear load); ≤ 7% THD (non-linear load) |
Connection |
Non-heating appliance connectors |
Коэффициент амплитуды (крест-фактор) (Current Crest Ratio) |
3 : 1 |
Работа при перегрузке (рабочий режим) (Overload behaviour in battery mode) |
up to 105% ± 5% continuous; > 105% ± 5% - < 150% ± 5% for 25 s; 150% ± 5% for 20 0ms |
up to 105% continuous; > 105% - < 130% for 10 min; 130% for 1 s |
Overload behaviour width existing mains |
up to 105% ± 5% continuous; > 105% ± 5% - <150% ± 5% for 30 s; 150% ± 5% for 300 ms Then automatic inverter to Bypass in < 4 ms (switches back when overload damps = load < 90%) |
up to 105% continuous; > 105% for 10 s Then automatic inverter to Bypass in 0 ms (switches back when overload damps = load < 90%) |
Short circuit behavior |
3 x IN for 140 ms |
Battery |
Время автономной работы при полной загрузке с акк. бат. (Autonomy time (full load width internal battery)) |
6 min |
at least one battery module required |
Номинальное напряжение (Rated direct voltage (intermediate circuit)) |
36 V |
96 V |
240 V |
Ток для зарядки батарей (Battery charging current) |
1 A / 7 A |
1 A / 9.6 A |
2 A |