Thyro-S

Thyristor Switch
Secure, fast, economic and communication capable

Advanced Energy THYRO S
The new communication capable thyristor switch Thyro-S is equipped with  advanced functions and system features to handle an extended application field.

As a connection-ready thyristor switch with secure operational behavior and load monitoring, the Thyro-S switches currents, voltages and power sources. It can be connected to bus systems, used in standalone operation, or used in conjunction with process controllers, PLC and computer systems. Used with the AEG Thyro- Tool Family programming software, it  provides for quick commissioning and simple visualization. Because it is simple to mount, easy to handle and commission, the new Thyro-S type thyristor switch is an excellent choice for a wide field of applications in process technology, e.g. in the areas of:

  • ovens (industrial, diffusion, drying)
  • plant equipment (extruders, plastic presses)
  • chemical industry (pipe trace heaters, pre-heating equipment)
  • glass processing (drying coatings)
  • automotive industry (e.g. paint drying equipment)
  • printing machines (IR drying)
  • packaging industry (shrink tunnels)

Брошюра Thyro-SБрошюра Thyro-S

Key FeaturesKey Features

In addition to wear-free operation and high effi ciency, this product series features:

  • simple handling and small space requirements
  • voltage ratings 230 V, 400 V, 500 V
  • current ratings 16 A ... 280 A
  • integrated semiconductor fuse
  • standard system interface for connection to an optional bus module (e.g. Profi bus-DP, ModBus RTU, CANopen, DeviceNet)
  • LED status indicators
  • operational modes 1:1, as well as 1:2, 1:3, 1:5 (e.g. for commissioning)
  • 24 V logic signal control (> 3V) or over standard system interface
  • secure isolation between control and power sections
  • single phase (3-phase structure by connecting two Thyro-S units)
  • UL approval, UL508 A (100 kA S.C.C.R.)
  • meets ISO 9001 quality standards
  • CE compliant

Наверх

Extras for the … HRL1 typeExtras for the … HRL1 type

  • additional 24V DC/AC electronic power supply
  • load monitoring
  • alarm relay

Наверх

Specification. Type series and specifi cation (excerpt)Specification. Type series and specifi cation (excerpt)

THYRO-1S

Current

Type Rating (kW)

Dissipation

Dimensions (mm)

Weight (kg)

H1, HRL1

(A)

230 V

400 V

500 V

(W)

W

H

D

approx.

 

16

3.7

6.4

8

30

45

121

127

0.7

 

30

6.9

12

15

47

45

121

127

0.7

 

45

10

18

22.5

48

52

190

182

1.7

 

60

14

24

30

80

52

190

182

1.7

 

100

23

40

50

105

75

190

190

1.9

 

130

30

52

65

150

125

320

237

4

 

170

39

68

85

210

125

320

237

4

..F..

280

64

112

140

330

125

370

237

5

VOLTAGE RATINGS

 

230 Volt – 57 % + 10 %;

for H 1

 

230 Volt – 15 % + 10 %;

> 99 V for H RL 1 with additional
24 AC/DC electronic power supply

 

400 Volt – 57 % + 10 %;

for H 1

 

400 Volt – 15 % + 10 %;

> 172 V for H RL 1 with additional
24 AC/DC electronic power supply

 

500 Volt – 57 % + 10 %;

for H 1

 

500 Volt – 15 % + 10 %;

> 215 V for H RL 1 with additional
24 AC/DC electronic power supply

LINE FREQUENCY

 

all types

47 Hz to 63 Hz

 

max. frequency change 5 % per half cycle

LOAD TYPE

 

Ohmic load

OPERATIONAL MODES

Name

Load signal for digital set-point = on

 

1 : 1

=

all full waves (default setting)

 

1 : 2

=

every 2nd full line cycle

 

1 : 3

=

every 3rd half line cycle (DC free)

 

1 : 5

=

every 5th half line cycle (DC free)

DIGITAL SET-POINT INPUTS (SWITCH-ON SIGNALS)

 

set-point 1

logic input 0 … 24 V Ri > 3,3 kΩ ON > 3 V

 

set-point 2

system interface, connection to controlling automation system via optional bus module

RELAY OUTPUT

 

1 changeover contact

AMBIENT TEMPERATURE

 

45 °C by passive convection cooling

 

35 °C by external fan cooling (type …F has inegrated fan)

 

Operation at higher temperatures is permissible with reduced current limits

 

temperature range to 55 °C: current rating reduction of -2 % / °C

 

With UL applications max. 40 °C